Universal Temperature Converter KFD2-UT2-Ex1
1-channel isolated barrier
24 V DC supply (Power Rail)
Thermocouple, RTD, potentiometer or voltage input
Current output 0/4
參考價 | 面議 |
更新時間:2023-10-30 17:26:10瀏覽次數(shù):632
聯(lián)系我們時請說明是化工儀器網(wǎng)上看到的信息,謝謝!
德國倍加福P+F輸入安全柵KFD2-UT2-Ex1正品現(xiàn)貨
參數(shù)表節(jié)選:的技術(shù)參數(shù) KFD2-UT2-Ex1
產(chǎn)品闡述
Current output 0/4 mA ... 20 mA
一般特性
Signal type Analog input
供電
連接器 terminals 14+, 15- or power feed module/Power Rail
額定電壓 20 ... 30 V DC
紋波 在電源容限內(nèi)
Power dissipation/power consumption ≤ 0.98 W / 0.98 W
輸入
德國倍加福P+F輸入安全柵KFD2-UT2-Ex1正品現(xiàn)貨
連接器 terminals 1, 2, 3, 4
RTD type Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995)
type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94)
type Cu10, Cu50, Cu100 (P50353-92)
type Ni100 (DIN 43760)
Measuring current approx. 200 µA with RTD
Types of measuring 2-, 3-, 4-wire connection
Lead resistance max. 50 Ω per line
Measuring circuit monitoring sensor breakage, sensor short-circuit
Thermocouples type B, E, J, K, N, R, S, T (IEC 584-1: 1995)
type L (DIN 43710: 1985)
type TXK, TXKH, TXA (P8.585-2001)
Cold junction compensation external and internal
Measuring circuit monitoring sensor breakage
電位器 0 ... 20 kΩ (2-wire connection), 0.8 ... 20 kΩ (3-wire connection)
電壓 selectable within the range -100 ... 100 mV
輸入電阻 ≥ 1 MΩ (-100 ... 100 mV)
輸出
連接器 output I: terminal 7: source (-), sink (+), terminal 8: source (+), terminal 9: sink(-)
輸出 模擬量電流輸出
電流范圍 0 ... 20 mA or 4 ... 20 mA
錯誤信號 downscale 0 or 2 mA, upscale 21.5 mA (acc. NAMUR NE43)
Source load 0 ... 550 Ω
open-circuit voltage ≤ 18 V
Sink Voltage across terminals 5 ... 30 V. If the current is supplied from a source > 16.5 V,
series resistance of ≥ (V - 16.5)/0.0215 Ω is needed, where V is the source voltage.
The maximum value of the resistance is (V - 5)/0.0215 Ω.